top of page

​​FSCU: FriconUSA Small-Sized Condensing Unit

The most common commercial refrigeration applications are centralized refrigeration for small and medium-sized supermarkets, cold rooms, blast coolers or freezers, continuous rapid cooling tunnels, block or flake ice-making machines, thermal ice storage, etc.

​​FSCU: FriconUSA Small-Sized Condensing Unit

STANDARD SERIES

Application Temperature:

“M” Medium: +35°F (+1.7°C) to 0°F (-18°C)

“L” Low: 0°F (-18°C) to -40°F (-40°C)

PREMIUM SERIES

Application Temperature:

“H” High: +45°F (+7.2°C) to +10°F (-12.2°C) SST

“M” Medium: +30°F (-1.1°C) to -20°F (-29°C) SST

“L” Low: +5°F (-15°C) to -40°F (-40°C) SST

“X” Extra Low, 2-stage: -15°F (-26°C) to -60°F (-51°C) SST

The FSCU: FriconUSA Small-Sized Condensing Unit, air-cooled condenser, is built with the best components in the market including Bitzer semi-hermetic compressors; available in capacities from 3 to 27 HP in configurations of a single compressor, or dual and triple parallel compressors.

 

The high quality and efficiency of our products allow us to ensure our clients a highly reliable operation, low energy consumption, and long equipment service life.

Eco-Friendly

​Premium Series

  • Bitzer Ecoline semi-hermetic compressor(s) with spring mounted vibration insulation, crankcase heater and internal thermal protection. For Extra “X” Low application temperature, a Bitzer two-stage semi-hermetic compressor is used.

  • Step unloader(s) on each compressor (4 cylinders: 50-100%, 6 cylinders: 33-66-100%).

  • Aluminum structure with galvanized steel reinforcement, high efficiency condenser with reinforced structure and aluminum micro-channel coils. Its low weight and size reduces the costs of transportation, installation and construction.

  • Galvanized and powder coated weatherproof cabinet.

  • EcoFriendly; Air cooled micro-channel condenser coil with internal volume reduced requires between 40% and 60% less refrigerant charge and results in a significant reduction of the refrigerant charge necessary for normal or flooded operations.

  • Wide range of SST (Saturated Suction Temperature).

  • Top and rear fan covers are designed to be easily interchangeable.

  • Quiet, high efficiency, external rotor motor, AC type axial fan(s) for a better operation, configured in a vertical position.

  • Vertical liquid receiver with inlet and outlet insulate valves, stainless steel relief valve at 450 PSI and electronic low liquid level indicator.

  • Liquid sight glass and solenoid valve.

  • Sealed suction filter and liquid drier for single compressor units. Replaceable core filter for units over 15 HP and all units with dual and triple compressors.

  • Suction accumulator.

  • Flexible joint on suction and discharge lines on each compressor.

  • Helical oil separator with discharge check valve and replaceable 5 micron oil filter, additionally, for units with dual or triple compressors, built-in oil reservoir.

  • Electronic oil level regulator for units with dual or triple compressors.

  • Electronic oil pressure switch.

  • Refrigerant: R-404a

  • Factory pre-charged with nitrogen and electrical work tested.

  • UL 508A listed built-in electrical control panel.

  • Compressor and fan circuit breakers.

  • Voltage and phase-loss monitor with protection module for each compressor.

  • Control: 208-230V / 1PH / 60HZ

  • Power Supply Voltage 208-230V / 3PH / 60HZ with single point power connection.

  • Electronic Control System; compressor(s) and condenser fan(s) operational management: alarms, measurement of pressure and temperature variables, 132x64 LCD backlit built-in display with 6-button keypad.

  • Alarm management: 3 alarms per compressor(s) (overload, pressure and oil) and 1 overload alarm for condenser fan(s).

  • Fixed high pressure controls on each compressor.

  • BMS (Building Management System): ModBus protocol for supervisor or HMI (Human Machine Interface).

  • 2-year warranty.

 

​Standard Series

  • Bitzer Ecoline Semi-Hermetic compressor(s) with spring-mounted vibration insulation, crankcase heater, and internal thermal protection.

  • Aluminum structure with galvanized steel reinforcement, high-efficiency condenser with reinforced structure, and aluminum micro-channel coils. Its low weight and size reduce the costs of transportation, installation, and construction.

  • A galvanized and powder-coated cabinet designed for outdoor use.

  • EcoFriendly; Air-cooled micro-channel condenser coil with internal volume reduced requires between 40% and 60% less refrigerant charge and results in a significant reduction of the refrigerant charge necessary for normal or flooded operations.

  • Wide range of SST (Saturated Suction Temperature).

  • Quiet, high efficiency, external rotor motor, AC-type axial fan(s) for better operation.

  • Vertical liquid receiver with inlet and outlet insulate valves, stainless steel relief valve at 450 PSI.

  • Sealed suction filter and liquid drier for single compressor units. Replaceable core filter for units over 15 HP and all units with dual and triple compressors.

  • Flexible joint on suction and discharge lines on each compressor.

  • Helical oil separator with discharge check valve, replaceable 5-micron oil filter, and built-in oil reservoir for units with dual or triple compressors.

  • Electronic oil level regulator for units with dual or triple compressors.

  • Electronic oil pressure switch.

  • Refrigerant: R-404a

  • Factory pre-charged with nitrogen and electrical work tested.

  • UL 508A listed a built-in electrical control panel.

  • Compressor and fan circuit breakers.

  • Voltage and phase-loss monitor for each compressor.

  • Control: 208-230V / 1PH / 60HZ

  • Power Supply Voltage 208-230V / 3PH / 60HZ with single-point power connection.

  • Electronic Control System; compressor(s) and condenser fan(s) operational management: alarms, measurement of pressure and temperature variables, 132x64 LCD backlit built-in display with a 6-button keypad.

  • Alarm management: 1 general alarm for the compressor(s) and 1 overload alarm for condenser fan(s).

  • Fixed high-pressure controls on each compressor.

  • BMS (Building Management System): ModBus protocol for supervisor or HMI (Human Machine Interface).

  • 1-year warranty.

Get a Quote

Submit a request and we'll reach out asap!

Thanks for submitting!

bottom of page