top of page

FWPS: FriconUSA Water Pump Station

​Applications: Chilled or Condensed water or Hot water

FWPS MEDIA_edited.png

The FWPS-V: FriconUSA Water Pump Station Vertical series delivers high e ciency performance that minimizes operation and energy costs. Vertically mounted pump and top suction and discharge manifold ts where most pumps cannot.

 

The unit features 1, 2 or 3 double volute design pumps with robust ductile iron construction. The FWPS is designed to be installed within a small footprint, give you low operating, installation and maintenance costs.

logos_edited_edited.png
  • Hot-dip galvanized, carbon steel bolted structure.

  • 1, 2 or 3 vertical closed coupling centrifugal pump(s). Double volute design extends seal and bearing life, minimizes noise and vibration, & improves operating efficiency.

  • Maximum pressure design 125 psi.

  • Pump Motor: High efficiency ODP for indoor operation.

  • Flange connections on both sides of the manifolds.

  • Suction and discharge butter y valve on each pump. 

  • Discharge waffle check valves.

  • Low pressure drop suction filter strainer.

  • Anti-vibration, rubber expansion joint in the suction and discharge of the pump.

  • UL 508A listed built-in electrical control panel.

  • Control 208-230V / 1PH / 60HZ.

  • Power Supply Voltage 460V / 3PH / 60HZ with single point power connection.

  • Electronic control system; pump operational management, rotation, thermal overload alarm, measurement of pressure and temperature variables, 132x64 LCD backlit built-in display with 6-button keypad.

  • 2 year warranty.

​

PUMP CHARACTERISTICS:

  • Vertically mounted top suction and discharge pump.

  • Ductile iron construction: ASTM A536 65-45-12.

  • Stainless steel shaft reduces possibility of oxidation: AISI 303.

  • Silicon bronze trimmed and balanced impeller: ASTM B584 UNS C876000.

  • Mechanical seal, type 21 John Crane, constructed and available in various con gurations to meet application requirements.